8.1 Standard Models
8-3
Chap. 8 SPECIFICATIONS
8.1.3 Single-phase 200 V series
FRN_ _ _ _C2S-7, where = A, C, E, or U
Item Specifications
Type (FRN_ _ _ _C2S-7) 0001 0002 0004 0006 0010 0012
Nominal applied motor (kW) *
1
( = A ,C or E)
0.1 0.2 0.4 0.75 1.5 2.2
Nominal applied motor (HP) *
1
( = U)
1/8 1/4 1/2 1 2 3
Rated capacity (kVA) *
2
0.30 0.57 1.3 2.0 3.5 4.5
Rated voltage (V) *
3
Three-phase, 200 to 240 V (with AVR function)
Rated current (A) *
4
0.8
(0.7)
1.5
(1.4)
3.5
(2.5)
5.5
(4.2)
9.2
(7.0)
12.0
(10.0)
Overload capability
150% of rated current for 1 min.
150% of rated current for 1 min or 200% of rated current for 0.5 s (for the rated
current given in parentheses)
Output Ratings
Rated frequency (Hz) 50 / 60 Hz
Phases, voltage, frequency Single-phase, 200 to 240 V, 50/60 Hz
Voltage and frequency
variations
Voltage: +10 to -10%, Frequency: +5 to -5%
(w/ DCR) 1.1 2.0 3.5 6.4 11.6 17.5
Rated current
(A) *
5
(w/o DCR) 1.8 3.3 5.4 9.7 16.4 24.0
Input Ratings
Required power supply
capacity (kVA) *
6
0.3 0.4 0.7 1.3 2.4 3.5
Braking torque (%) *
7
150 100 50 30
DC braking
Starting frequency*
8
: 0.0 to 60.0 Hz, Braking time: 0.0 to 30.0 s,
Braking level: 0 to 100%
Braking
Transistor for
braking resistor
-- Built-in
Applicable safety standards UL508C, EN61800-5-1: 2007
Enclosure IP20 (IEC 60529:1989), UL open type (UL50)
Cooling method Natural cooling Fan cooling
Mass (kg) 0.6 0.6 0.7 0.9 1.8 2.5
Mass (lbs) 1.3 1.3 1.5 2.0 4.0 5.5
*1 Fuji 4-pole standard motors.
*2 Assuming the rated output voltage as 220 V.
*3 Output voltages cannot exceed the power supply voltage.
*4 The load shall be reduced so that the continuous operating current is the rated current in parentheses or less if the
carrier frequency is set to 3 kHz or above or the ambient temperature exceeds 40°C (104°F).
*5 Estimated value to apply when the inverter is connected to the power supply of 500 kVA (inverter capacity x 10
when the inverter capacity exceeds 50 kVA) and %X = 5%.
*6 Obtained when a DC Reactor (DCR) is used.
*7 Average braking torque when a motor of no load decelerates from 60 Hz. (It varies with the efficiency of the
motor.)
*8 Effective function only in induction motor drive.
Note: A box () in the above table replaces A, C, E, or U depending on the shipping destination.
A: Asia, C: China, E: EC, U: USA