8-16
Item Max.
ON level 2V
Operation
voltage
OFF level 27V
Maximum load current at ON
50mA
Leakage current at OFF
0.1mA
Analog output, transistor output, and relay output terminals
Classifi-
cation
Symbol Name Functions
Related
function
codes
[FMA] Analog monitor
The monitor signal for analog DC voltage (0 to +10
VDC) is output. The signal functions can be selected
with the function code F31 from the following.
• Output frequency (before slip compensation)
• Output frequency (after slip compensation)
• Output current • Output voltage
• Input power • PID feedback value
• DC link bus voltage • Analog output test (+)
• PID command (SV) • PID output (MV)
(Output voltage: 0 to +10 VDC,
maximum current: 2 mA
Up to two analog voltmeters can be connected.)
F30, F31
Analog output
[11] Analog common Common for analog output signal ([FMA])
This terminal is electrically isolated from terminals
[CM] and [Y1E].
Possible to assign various signals to terminals [Y1]
using function code E20. For details, refer to Section
9.2.2 "E codes."
Normal/negative logic output switching feature:
Switches the logic value (1/0) for ON/OFF of the
terminals between [Y1] and [Y1E]. If the logic value
for ON between [Y1] and [Y1E] is 1 in the normal
logic system, for example, OFF is 1 in the negative
logic system.
Digital output circuit specification
Figure 8.5 shows examples of connection between the
control circuit and a PLC.
E20
[Y1] Transistor output
• Check the polarity of an external power
input.
• To connect a control relay, connect a
surge absorbing diode across the coil of
the relay.
Transistor output
[Y1E]
Transistor output
common
Common for transistor output signal
(Isolated from terminals [CM] and [11].)