9-6
E codes: Extension Terminal Functions
Code Name Data setting range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
(Note)
Refer
to
page:
E01 Terminal [X1] Function Selecting function code data assigns the
corresponding function to terminals [X1] to [X3]
as listed below.
N Y 0 9-47
E02 Terminal [X2] Function 0 (1000): Select multistep frequency (SS1)–
N Y 7
E03 Terminal [X3] Function 1 (1001): Select multistep frequency (SS2)–
N Y 8
2 (1002): Select multistep frequency (SS4) 
3 (1003): Select multistep frequency (SS8) 
4 (1004): Select ACC/DEC time (RT1)
6 (1006): Enable 3-wire operation (HLD)
7 (1007): Coast to a stop (BX)
8 (1008): Reset alarm (RST)
9 (1009): Enable external alarm trip (THR)
10 (1010): Ready for jogging (JOG)
11 (1011): Select frequency command 2/1
(Hz2/Hz1)
12 (1012): Select motor 2/motor 1 (M2/M1)
13: Enable DC braking (DCBRK)
17 (1017): UP (Increase output frequency)
(UP)
18 (1018): DOWN (Decrease output
frequency) (DOWN)
19 (1019): Enable data change with keypad
(WE-KP)
20 (1020): Cancel PID control (Hz/PID)
21 (1021): Switch normal/inverse operation
(IVS)
24 (1024): Enable communications link
via RS-485 (LE)
33 (1033): Reset PID integral and differential
components (PID-RST)
34 (1034): Hold PID integral component
(PID-HLD)
Setting the value in parentheses ( ) shown
above assigns a negative logic input
(Active-OFF) to a terminal.
Note that, in the case of THR, data "1009" is for
normal logic (Active-ON) and "9," for negative
logic (Active-OFF).
Signals having no value in parentheses ( )
cannot be used for negative logic.
E10 Acceleration Time 2 0.00 to 3600
Note: Entering 0.00 cancels the acceleration
time, requiring external soft-start and -stop.
0.01 s Y Y 6.00 9-57
E11 Deceleration Time 2 0.00 to 3600
Note: Entering 0.00 cancels the deceleration
time, requiring external soft-start and -stop.
0.01 s Y Y 6.00
E20 Terminal [Y1] Function
N Y 0 9-58
E27
Selecting function code data assigns the
corresponding function to terminals [Y1] and
[30A/B/C] as listed below.
0 (1000): Inverter running (RUN)
N Y 99
Terminal [30A/B/C]
Function
1 (1001): Frequency arrival signal (FAR)
2 (1002): Frequency detected (FDT)
3 (1003): Undervoltage detected
(Inverter stopped) (LU)
5 (1005): Inverter output limiting (IOL)
6 (1006): Auto-restarting after momentary
power failure (IPF)
7 (1007): Motor overload early warning (OL)
26 (1026): Auto-resetting (TRY)
30 (1030): Service lifetime alarm (LIFE)
35 (1035): Inverter running 2 (RUN2)
36 (1036): Overload prevention control
(OLP)
37 (1037): Current detected (ID)
38 (1038): Current detected 2 (ID2)
(Note) Alphabets in the Default setting field denote shipping destination: A (Asia), C (China), E (Europe), and U (USA).