9-64
The FARFDT is an ANDed signal of FAR and FDT.
E34 Overload Early Warning/Low Current Detection (Level)
E35 Overload Early Warning/Low Current Detection (Timer)
E37 Current Detection 2 (Level)
E38 Current Detection 2 (Timer)
These function codes define the detection level and timer for the OL ("Motor overload early
warning"), ID ("Current detected"), ID2 ("Current detected 2") and IDL ("Low current
detected") output signals.
Detection level Timer
Motor
characteristics
Thermal time
constant
Output
signal
Data
assigned
to output
terminal
Range:
See below
Range:
0.01 to 600.00 s
Range:
See below
Range:
0.5 to 75.0 min
OL 7 E34 -- F10 F12
ID 37 E34 E35
ID2 38 E37 E38
IDL 41 E34 E35
-- --
- Data setting range
Operation level: 0.00 (Disable), 1 to 200% of inverter rated current
Motor characteristics 1: Enable (For a general-purpose motor and Fuji standard
permanent magnet synchronous motor with shaft-driven cooling
fan)
2: Enable (For an inverter-driven motor with separately powered
cooling fan)