9-76
C50
Bias (Frequency command 1) (Bias base point)
F18 (Bias, Frequency command 1)
For details about bias base point setting for frequency command 1, refer to the description of
F18.
C51 Bias (PID command 1) (Bias value)
C52 Bias (PID command 1) (Bias base point)
These function codes specify the gain and bias of the analog PID command 1, enabling it to
define arbitrary relationship between the analog input and PID commands.
The actual setting is the same as that of function code F18. For details, refer to the
description of F18.
Note that function codes C32, C34, C37 and C39 are shared by frequency
commands.
Bias value (C51)
- Data setting range: -100.00 to 100.00 (%)
Bias base point (C52)
- Data setting range: 0.00 to 100.00 (%)
C94 to C96 Jump Frequency 4, 5 and 6 C01 to C03 (Jump Frequency 1 to 3)
For details about this function, refer to the description of C01.
C99 Digital Reference Frequency F01 (Frequency Command 1)
C99 displays the digital reference frequency specified from the keypad (when F01 = 0). The
C99 data can be changed only via the communications link.
The copy function incorporated in the remote keypad or FRENIC Loader can copy the C99
data so that it is possible to copy the digital reference frequency.
C99 is available in the ROM version 0500 or later.