9-90
When HP rating IM (P99 = 1 or A39 = 1) are selected, the motor parameters are as
listed in the following tables. (HP refers to horse power that is used mainly in North
America as a unit of motor capacity.)
200 V class series, single-phase 100 V class series for all destinations,
230 V, 60 Hz, rated
voltage, base frequency
Motor capacity
(HP)
Rated
current
(A)
No-load
current
(A)
%R1
(%)
%X1
(%)
Rated slip
frequency
(Hz)
P02/A16
Nominal
applied
motor
(HP)
P03/A17 P06/A20 P07/A21 P08/A22 P12/A26
0.01 to 0.11 0.10 0.44 0.40 13.79 11.75 2.50
0.12 to 0.24 0.12 0.68 0.55 12.96 12.67 2.50
0.25 to 0.49 0.25 1.40 1.12 11.02 13.84 2.50
0.50 to 0.99 0.5 2.00 1.22 6.15 8.80 2.50
1.00 to 1.99 1 3.00 1.54 3.96 8.86 2.50
2.00 to 2.99 2 5.80 2.80 4.29 7.74 2.50
3.00 to 4.99 3 7.90 3.57 3.15 20.81 1.17
5.00 to 7.49 5 12.60 4.78 3.34 23.57 1.50
7.50 to 9.99 7.5 18.60 6.23 2.65 28.91 1.17
10.00 to 14.99 10 25.30 8.75 2.43 30.78 1.17
15.00 to 19.99 15 37.30 12.70 2.07 29.13 1.00
20.00 to 24.99 20 49.10 9.20 2.09 29.53 1.00
25.00 to 29.99 25 60.00 16.70 1.75 31.49 1.00
30.00 to 39.99 30 72.40 19.80 1.90 32.55 1.00
400 V class series for all destinations,
460 V, 60 Hz, rated voltage, base frequency
Motor capacity
(HP)
Rated
current
(A)
No-load
current
(A)
%R
(%)
%X
(%)
Rated slip
frequency
(Hz)
P02/A16
Nominal
applied
motor
(HP)
P03/A17 P06/A20 P07/A21 P08/A22 P12/A26
0.01 to 0.11 0.10 0.22 0.20 13.79 11.75 2.50
0.12 to 0.24 0.12 0.34 0.27 12.96 12.67 2.50
0.25 to 0.49 0.25 0.70 0.56 11.02 13.84 2.50
0.50 to 0.99 0.5 1.00 0.61 6.15 8.80 2.50
1.00 to 1.99 1 1.50 0.77 3.96 8.86 2.50
2.00 to 2.99 2 2.90 1.40 4.29 7.74 2.50
3.00 to 4.99 3 4.00 1.79 3.15 20.81 1.17
5.00 to 7.49 5 6.30 2.39 3.34 23.57 1.50
7.50 to 9.99 7.5 9.30 3.12 2.65 28.91 1.17
10.00 to 14.99 10 12.70 4.37 2.43 30.78 1.17
15.00 to 19.99 15 18.70 6.36 2.07 29.13 1.00
20.00 to 24.99 20 24.60 4.60 2.09 29.53 1.00
25.00 to 29.99 25 30.00 8.33 1.75 31.49 1.00
30.00 to 39.99 30 36.20 9.88 1.90 32.55 1.00