9-104
H92, H93
Continuity of Running (P and I)
F14 (Restart Mode after Momentary Power Failure)
For details, refer to the description of F14.
H94 Cumulative Run Time of Motor 1 A51 (Cumulative Run Time of Motor 2)
For details, refer to the description of H79.
H95
DC Braking (Braking response mode)
F20 to F22 (DC Braking 1,
Braking staring frequency, Braking level, and Braking time)
A09 to A11 (DC Braking 2,
Braking staring frequency, Braking level, and Braking time)
For setting of DC braking, refer to the descriptions of F20 to F22.
H96 STOP Key Priority/Start Check Function
H96 specifies a functional combination of "STOP key priority" and "Start check function" as
listed below.
Data for H96 STOP key priority Start check function
0 Disable Disable
1
Enable Disable
2
Disable
Enable
3
Enable Enable
STOP key priority
Even when a run command is entered from a digital input terminal (F02 = 1) or via the
RS-485 communications link (link operation), pressing the
key forces the inverter to
decelerate and stop the motor. After that,
er6
appears on the LED monitor.
Start check function
For safety, this function checks whether a run command has been turned ON or not in each of
the following situations. If it has been turned ON, the inverter does not start up with alarm
code
er6
displayed on the LED monitor.
• When the power to the inverter is turned ON.
• When the
key is pressed to release the alarm status or when the digital input terminal
command RST ("Reset alarm") is turned ON.
• When the run command source is switched by the digital input terminal command LE
("Enable communications link via RS-485").