Proportional band (Setting range: 0.0 to 999.9% of the measured range)
[Description]
• To select the ON/OFF control (two-position control), set
 to 0.0.  It is not necessary to set   and  .
•  can be automatically set by the auto-tuning operation.
• When   is too small, control will be unstable, and when
 is too large, the response will be delayed.
[Setting example] Changing the proportional band from 5.0% to 15.0%
• Set the hysteresis of the ON/OFF control (two-position
control) in the parameter 
 
.
• If auto-tuning is run after the ON/OFF control is selected,
the ON/OFF control changes to the PID control.  To keep
the ON/OFF control selected, do not execute the auto-
tuning.
   Related parameters: (page 23)
(page 32)
w Second block parameters
Press the           key once.     will be displayed and the 15.0% will be registered for    .  After that, 
the controller will operate with      being 15.0%. 
(Repeat the procedure from 2 to 4 to check the set value.)
Press and hold the           key for three seconds.
     will be displayed.
Press the           or           keys to flicker and to display       . 
Press the           key once.
The current setting (     ) will be displayed.