31
 
PV (Measured value) stable range (Setting range: 0 to 100%FS)
[Description]
• Self-tuning logic recognizes that control is stable if PV is
staying within the SV ±   .
[Setting example] Changing the PV stable range from 2 to 3
• It is not necessary to set this parameter under normal con-
ditions.
Press the           key once.             will be displayed and 3 will be registered for            .  After that, 
the controller will operate with the PV stable range being 3.
Press and hold the           key for three seconds.
    will be displayed.
Press the           or           keys to flicker and to display      .
(Repeat the procedure from 3 to 5 to check the set value.)
Press the           key once.
The current setting (      ) will be displayed.
Press the           key to display           .
SEL
SEL
SEL
1.
4.
If you want to display the operation status, press and hold the           key for two seconds.
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.
6.
2.
3.
SEL
5.
Display Operating procedure
PV indication
PV indication
SV indication