[Description]
• With this function, predetermined value is added to the origi-
nal SV. This parameter is used to eliminate the offset that
occurs in performing P control.
• The PXR3 operates based on the SV to which the SV off-
set value is added.
SV offset (Setting range: -50 to 50%FS)
[Setting example] Adding the SV offset value of 9°C to the currently set value
• Alarm judgment is made by the displayed SV to which
the SV offset value is not added.
• When the retransmission output type is set to the SV, the
displayed SV, to which the SV offset value is not added,
is output.
Press the key once. will be displayed and will be registered for .
(The displayed SV remains unchanged.) After that, the controller will operate at the SV value to
which the SV offset value of 9˚C is added.
Press and hold the key for three seconds.
will be displayed.
Press the or keys to flicker and to display .
(Repeat the procedure from 3 to 5 to check the set value.)
Press the key once.
The current setting ( ) will be displayed.
Press the key to display .
SEL
SEL
SEL
1.
4.
If you want to display the operation status, press and hold the key for two seconds.
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.
6.
2.
3.
SEL
5.
Display Operating procedure
PV indication
PV indication
SV indication