Troubleshooting
Remedies
Set the parameter of 
 
 correctly.
Correct the polarity of the input signal on the
PXR3.
Set the parameter of 
 
 to 3, and check if the tem-
perature around an ordinary temperature is displayed.
(Thermocouples B and R have a large error around ordi-
nary temperatures.  However, this is not a fault.)
Ask to make adaptations on your model.  Or
replace your model with a new one.
Tighten the connecting cables.
Replace the sensor with a new one.  Or remove
the short-circuit.
Replace the sensor or other input devices with
new ones.
Set the parameters again so that the value of
 
is smaller than the value of 
 
.
Set the parameters again so that the difference of
the set values of 
 and    is made larger.
Set the parameters of 
 
and
   
 again
according to the input range table.
Set the parameters of   and
 
 
 again
so that the measured range is 9999 or less.
Set the parameter of   to "1" or "2".
Set all the parameters again.  (When the set values of the param-
eters of   ,  , and   are changed, the
set value of each parameter for which "*" is marked at the  page
number of the reference page in the Parameter list, are changed.)
Set   to "0", and return 
 
 to an
original value.
Set the parameter 
 
 to 0.0.
 Adjust the set value of parameter 
 
 to be
suitable for the device to be controlled.
Set the parameter 
 
 correctly.
Perform the auto-tuning.
Decrease the set value of the parameters 
and
   
 gradually.
Set the parameters 
 
,
   
,
 
and 
 
 again to be suitable for the
process.
Set the parameter   again to be suitable
for the process.
Symptoms
1. The display has shown
 or 
 
.
2.
   has been dis-
played.
3. A decimal point has not
been displayed.
4. The SV or the set val-
ues of some parameters
have been changed
without any operation.
5. ON/OFF control (Two-posi-
tion control) has not started.
6. ON/OFF control is not
functioning properly.
7. The Micro-controller is
not controlling prop-
erly.
Possible causes
q The setting of     is not correct for
the input signals of sensors or others.
w The polarity of the input signal does not
match that of the PXR.
e Input terminals are short-circuited in ther-
mocouple B or R.  (
 
 
= 4, 5)
r
The input signals and type of sensors or others
do not match those of the controller you use.
t
The connecting cables for the sensor are loose.
y A break or short-circuit occurred in the
sensor.
u The sensor or other input devices that are
connected to the PXR3 have problems.
i The set value of the parameter of 
is larger than the value of 
 
.
o The measured value is too large or too
small.
q
The value of 
 
 is set to 3277°C or more
for thermocouple and resistance bulb input.
w
The measured range (
   
to
   
) is set
to 10000 or more for voltage and current input.
"0" is set in the parameter of 
 
 
.
q The parameter of 
 
, 
   
, or
 
 was changed.
w When the set value of 
 
is larger than
1000, "1" is registered for
 
.
0.0 is not set in the parameter 
.
q The set value of parameter 
 
 is not
correct.
w
The setting of parameter 
 
is not correct.
q The set values of the parameters 
 
,
   
,
and
 
 
are not correct.
w The cycle times are too long.
e Output is limited.
r Output is not limited correctly.
Reference
pages
Page 35
Page 35
-
-
-
-
Page 36
Page 36
Page 36
Page 36
Page 38
Page 36
Page 34
Page 20
Page 23
Page 32
Page 16
Page 33
Page 56
Page 57
This section explains the judgments and remedies for problems.