[Description]
• These parameters are used for setting the lower and up-
per limits of the measured range.
• A decimal point position can be set in the parameter of
.
• For the current and voltage inputs, = , , and for
other inputs, = are valid.
• See the right table for input range.
Setting lower limit of the measuring range (Setting range: -1999 to 9999)
Setting upper limit of the measuring range (Setting range: -1999 to 9999)
Selection ˚C / ˚F (Setting: ˚C or ˚F )
w Input range table (Standard range)
J
J
K
K
K
R
B
S
T
T
E
E
N
PL-II
1 to 5 V DC
Thermocouple
Direct-curren
t
voltage
-1999 to 9999
(Scaling is possible)
Settable up
to 2 digits
* For 4 to 20 mA DC input, connect a resistance of 250Ω between
terminals ② and ③ to change the input to the 1 to 5 V DC input.
[Note]
The input accuracy is ±0.5%FS±1 digit except the cases shown
below.
Thermocouple R at 0 to 400 °C: ±1%FS ± 1 digit ±1˚C
Thermocouple B at 0 to 500 °C: ±5%FS ± 1 digit ±1˚C
Other kinds of thermocouples : ±0.5% FS ± 1 digit ±1˚C
150
300
500
600
100
200
600
850
400
800
400
800
1200
1600
1800
1600
200
400
800
800
1300
1300
Range
(°C)
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
0
0
0
0
-50
-100
-150
-150
0
0
0
0
0
0
0
0
-150
-150
0
-150
0
0
302
572
932
1112
212
392
1112
1562
752
1472
752
1472
2192
2912
3272
2912
392
752
1472
1472
2372
2372
Range
(°F)
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
32
32
32
32
-58
-148
-238
-238
32
32
32
32
32
32
32
32
-238
-238
32
-238
32
32
With / without
a decimal point
(°C)
O
O
O
O
O
O
O
X
O
O
O
O
X
X
X
X
O
O
O
O
X
X
Pt100Ω
Resistance
bulb JIS
(IEC)
Input type
*
With / without
a decimal point
(°F)
O
O
O
X
O
O
X
X
O
X
O
X
X
X
X
X
X
X
X
X
X
X
*
O: with
X: without
*