Cycle time of control output 1 (Setting range: 1 to 150 seconds)
[Description]
• This parameter is applicable for to the contact output and
SSR-driving output.
• While input is within the proportional band, output
changes between ON and OFF in cycles.  These cycles
are called cycle time.
For contact output:
The higher the frequency of output is, the more precise
the control becomes.  However a high frequency of out-
put may shorten the life of the contacts and the device to
be controlled.  Be sure to adjust the proportional cycles
considering controllability and the life of the device and
the contacts.
Typical: 30 seconds
For SSR-driving output:
Use in short cycles if there is no problem with the device
to be controlled.
Typical: 1 to 2 seconds
Output: ON
Cycle
time
Cycle
time
[Setting example] Setting the cycle time from 30 seconds to 20 seconds
• Do not set this parameter to "0".
Press the           key once.       will be displayed and 20 seconds will be registered for       .  
After that, the controller will operate with the cycle time being 20 seconds.
Press and hold the           key for three seconds.
    will be displayed.
Press the           or           key to flicker and to display      . 
(Repeat the procedure from 3 to 5 to check the set value.)
Press the           key once.
The current setting (      ) will be displayed.
Press the           key to display       .
SEL
SEL
SEL
1.
4.
If you want to display the operation status, press and hold the           key for two seconds.
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.
6.
2.
3.
SEL
5.
Display Operating procedure
PV indication
PV indication
SV indication