26
 
Output offset value (Setting range: -100.0 to 100.0 %)
 
Anti-reset windup (Setting range: 0 to 100%FS)
[Description]
• The anti-reset windup ( 
 
) is automatically set to an
optimum value by the auto-tuning operation.
By setting  , the amount of overshoot can be adjusted.
[Note]
By making use of the fuzzy control system equipped with
PXR, the amount of overshoot can be minimized without
setting   and  .
[Setting example] Changing the anti-reset windup from 60˚C to 80˚C.
PV
SV
}
}
}
AR value
AR value
In this range, the integral
operation is not performed.
In this range, the integral
operation is performed.
In this range, the integral
operation is not performed.
Press the           key once.        will be displaed and 80˚C will be registered for      .  After that, the 
controller will operate with the       being 80˚C. 
Press and hold the           key for three seconds.
    will be displayed.
Press the           or           keys to flicker and to display        .
(Repeat the procedure from 3 to 5 to check the set value.)
Press the           key once.
The current setting (       ) will be displayed.
Press the           key to display      .
SEL
SEL
SEL
1.
4.
If you want to display the operation status, press and hold the           key for two seconds.
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.
6.
2.
3.
SEL
5.
Display Operating procedure
PV indication
PV indication
SV indication