[Description]
• With this function, predetermined value is added to the in-
put reading.  This parameter is used for adjusting PXR3’s
indication so that it becomes same as the one of the re-
corder.
 
PV offset (Setting range: -10 to 10%FS)
[Setting example] Adding the PV offset value of 5°C to the input value of 1200 °C
• The PXR3 operates at the displayed PV (the value to
which the PV offset value is added).
Press the           key once.            will be displayed and    will be registered for           , and then offset
5˚C will be added to the input value.  After that, the controller will operate so that the value to
which the offset value of 5˚C is added can be brought close to the set value.
Press and hold the           key for three seconds.
    will be displayed.
Press the           or           keys to flicker and to display      .
(Repeat the procedure from 3 to 5 to check the set value.)
Press the           key once.
The current setting (       ) will be displayed.
Press the           key to display           .
SEL
SEL
SEL
1.
4.
If you want to display the operation status, press and hold the           key for two seconds.
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.
6.
2.
3.
SEL
5.
Display Operating procedure
PV indication
PV indication
SV indication