50
[Description]
These parameters set the setting range of the SV (Setting
value).
Both the SV under ramp-soak operation and the SV switched
by the DI1 function are affected by the SV limiter.
The SV upper and lower limiters (
,
) can be set
within the range of the measuring values (
,
).
SV (Setting value) lower limiter (Setting range: 0 to 100%FS)
SV (Setting value) upper limiter (Setting range: 0 to 100%FS)
[Note]
Before setting the parameters of and , be sure
to set the following parameters.
Setting the lower limit of the measured range ( )
Setting the upper limit of the measured range ( )
Setting the of decimal places point position ( )
After changing the parameters of , , and
, power off the PXR, and then on. Then, set the pa-
rameters of and again.
Before setting the SV, set the parameters of and
.
Be sure to set the values of and so that
is larger than or is the same as .
Although the displayed SV is affected by the limiter imme-
diately after setting and , the set values of
to are not affected.
When the SV limiter is set during ramp-soak operation or
switching the SV with the DI function, the SV (SV0) that is
set manually and the displayed SV are affected by the SV
limiter. So, after setting the ramp-soak operation to OFF,
or returning the switched SV to the original SV, the PXR3
operates with the SV0 affected by the SV limiter.
Lower limit of
measuring range
(P-SL)
SV lower
limiter
(SV-L)
Setting value
(SV)
SV upper
limiter
(SV-H)
Upper limit of
measuring range
(P-SU)
Measured value
(PV)
Setting range of the SV (Setting value)
Setting range of SV limiter [Measuring range (FS)]
[Setting example] Setting the upper limiter to 100°C
Press the key once. will be displayed and 100˚C will be registered for . After
that, the upper limit of the SV will be 100˚C.
Press and hold the key for five seconds.
will be displayed.
Press the or keys to flicker and to display .
(Repeat the procedure from 3 to 5 to check the set value.)
Press the key once.
The current setting ( ) will be displayed.
Press the key to display .
SEL
SEL
SEL
1.
4.
If you want to display the operation status, press and hold the key for two seconds.
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.