Input type for PYP (Setting range: 0 to 7, 32 to 47) (Option)
[Description]
• When the Color Touch-Operation Unit (Model: PYP)
made by Fuji Electric is connected to the PXR, this pa-
rameter makes the PYP recognize the measured range.
• When setting the same temperature range that is set in
the input range, P-SL, and P-SU of the PXR, the read-
ings between the PXR and PYP are met.
00
01
02
03
04
05
06
07
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
Input type
Resistance bulb
JIS
IEC
Thermocouple
Pt100
J
J
K
K
K
R
B
T
T
E
E
S
N
U
WRe5 · 26
PLII
0 to 150
°C
0 to 300
°C
0 to 500
°C
0 to 600
°C
-50 to 100
°C
-100 to 200
°C
-150 to 600
°C
-150 to 850
°C
0 to 400
°C
0 to 800
°C
0 to 400
°C
0 to 800
°C
0 to 1200
°C
0 to 1600
°C
0 to 1800
°C
-199.9 to 200
°C
-150 to 400
°C
0 to 800
°C
-199.9 to 800
°C
0 to 1600
°C
0 to 1300
°C
-199.9 to 400
°C
0 to 2300
°C
0 to 1300
°C
Set value
Temperature range(°C)
[Setting example] Setting the input range of the PXR3 to thermocouple B
If you want to display the operation status, press and hold the key for two seconds.
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.
Press the key once.
will be displayed and (Thermocouple B) will be registered for the input range.
After that, PYP will recognize the input range of the PXR3 as thermocouple B ( 0 to 1800˚C).
Press and hold the key for five seconds.
will be displayed.
Press the or keys to flicker and to display .
(Repeat the procedure from 3 to 5 to check the set value.)
Press the key once.
The current setting ( ) will be displayed.
Press the key to display .
SEL
SEL
SEL
1.
4.
6.
2.
3.
SEL
5.
Display Operating procedure
PV indication
PV indication
SV indication