[Setting example] Setting the 1st target SV to 400°C
PV
200
100
50
TM1r TM1S
TM3r
TM3S
SV-1
SV-2
PV
TM1r TM1S
TM2S
TM3r
SV-3
TM2r
Pattern of the program
Pattern that is affected
by the SV limit function
• The segment in which both the ramp time and soak time
are set to "0" is skipped.
[Ex]
SV-1: 50 SV-2:200 SV-3:100
TM1r:0.10 TM2r:0.00 TM3r:1.00
TM1S:0.05 TM2S:0.00 TM3S:0.75
• The SV limit function is valid even while the ramp-soak
operation is running.
Although the set value (SV-n) remains unchanged, the
SV under ramp-soak operation is affected by the limit
function. Therefore, the pattern is as shown in the figure
on right, and it may not change according to the original
set time.
Press the key once. will be displayed and 400˚C will be registered for the 1st target
value.
Press and hold the key for three seconds.
will be displayed.
Press the keys to flicker and to display .
(Repeat the procedure from 3 to 5 to check the set value.)
Press the key once.
The current setting ( ) will be displayed.
Press the key to display .
SEL
SEL
SEL
1.
4.
If you want to display the operation status, press and hold the key for two seconds.
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.
6.
2.
3.
SEL
5.
Display Operating procedure
PV indication
PV indication
SV indication