CONTROLLER AND CONVERTOR
Model
Maximum
connectable
units in one VRF
network system
Remarks
Controller
Central Control
System
Controller
UTY-APGX 1
*1:Note
Max.controllable VRF network system : 4
Max.controllable remote controller
groups : 1600 per 4 VRF network system
Max.controllable indoor unit : 1600 per 4
VRF network system
Max.controllable groups : 1600 per 4
VRF network system
System
Controller Lite
UTY-ALGX 1
Max.controllable VRF network system : 1
Max.controllable remote controller
groups : 400
Max.controllable indoor unit : 400
Max.controllable groups : 400
Touch Panel
Controller
UTY-DTG
16
*2:Note
Max.controllable remote controller
groups : 400
Max.controllable indoor unit : 400
Max.controllable groups : 400
Central
Remote
Controller
UTY-DCG
16
Max.controllable indoor unit : 100
Max.controllable groups : 16
Group Remote
Controller
UTY-CGG
(64)
When Group Remote Controller is used,
Network Convertor (UTY-VGGXZ1) is
required.
Max controllable remote controller
groups : 8
Max controllable indoor units : 18
Individual Control
Wired Remote
Controller
UTY-RNR
Max controllable indoor units : 9
UTY-RLR
Max controllable indoor units : 9
UTY-RNK
Max controllable indoor units : 9
Simple Remote
Controller (with
master control)
UTY-RSK
Max controllable indoor units : 9
Simple Remote
Controller
(without master
control)
UTY-RHK
Max controllable indoor units : 9
Wireless
Remote
Controller
UTY-LNH
*1 Note: Different VRF series may be connected for each of the 4 VRF networks supported by the
unit, but different series may not coexist within the same network.
(VR-II Series, V-III Series, V-II Series, J-II Series and J-IIS Series can exist together on same
network. V Series and S Series can exist together on same network, too.)
*2 Note : For one VRF network system, total number of Touch Panel Controller, Central Remote
Controller, Network Convertor for Group Remote Controller is 16, including one Network
Convertor for L
ON
W
ORKS
®
.
- (06 - 07) -
SYSTEM
DESIGN
SYSTEM
DESIGN