Model
Maximum
connectable
units in one VRF
network system
Remarks
Adaptor / Convertor
Signal
Amplier
UTY-VSGX Z1 8
The signal amplier is required when
500m or more in transmission line length
or connected unit exceeds 64units.
Network
Convertor
UTY-VGGXZ1
Used for
connecting split
system : 100
Total number
of refrigerant
system and
Network
convertor is
maximum 100.
Max connectable Single split or Big multi
type in a UTY-VGGXZ1 : 16 units.
Used for
connecting
Group Remote
Controller : 16
*2:Note
Max connectable Group Remote
Controller : 4 units.
One Network Convertor (UTY-VGGXZ1)
covers 2 refrigerant systems.
Network
Convertor for
L
ON
W
ORKS
®
UTY-VLGX 1 Max controllable indoor units : 128
BACnet
®
Gateway
UTY-ABGX 1
*1:Note
Max.controllable VRF network system : 4
Max.controllable remote controller
groups : 1600 per 4 VRF network system
Max.controllable indoor unit : 1600 per 4
VRF network system
Max.controllable groups : 1600 per 4
VRF network system
External
Switch
Controller
UTY-TEKX Max connectable indoor units : 16
Service & Maintenance
Service Tool UTY-ASGX
1
1 Service
Tool or 1 Web
Monitoring
Tool can be
connected.
PC : Field supplied.
USB adaptor is required.
Web
Monitoring
Tool
UTY-AMGX
*1:Note
.
Web Monitoring Tool: Internet explorer
6.0 or higher.
PC : Field supplied.
USB adaptor is required.
Up to 4 VRF network system can be
observed with one Web Monitoring Tool.
*1 Note: Different VRF series may be connected for each of the 4 VRF networks supported by the
unit, but different series may not coexist within the same network.
(VR-II Series, V-III Series, V-II Series, J-II Series and J-IIS Series can exist together on same
network. V Series and S Series can exist together on same network, too.)
*2 Note : For one VRF network system, total number of Touch Panel Controller, Central Remote
Controller, Network Convertor for Group Remote Controller is 16, including one Network
Convertor for L