LOW STATIC PRESSURE DUCT / CONCEALED FLOOR TYPE
Ceiling concealed setting
z
Attached band
Supporter
Attached drain hose
Downward gradient
1/100 or more
Arrange the drain hose
lower than this position
1.5m to 2.0m
Air bleeding
Rise
Trap
Prohibited
Floor standing concealed setting
z
Upward
gradient
Interruption
of control box
Prohibited
OK
CAUTION
Connect the drain hose so that the control box cover can easily be removed for servicing
when necessary.
In order to prevent water from leaking into the control box, make sure that the piping is well
insulated.
After finishing the piping, the drain hose installation and the wiring, seal the holes in the
wall.
- (06 - 63) -
SYSTEM
DESIGN
SYSTEM
DESIGN