SLIM DUCT / SLIM CONCEALED FLOOR TYPE
Ceiling concealed setting
z
Drain hose
Arrange the drain hose
lower than this position
Drain cap
Supporter
1.5m to 2.0m
Prohibited
Trap
Rise
Air bleeding
Locally arranged pipe
Max.
300 mm
VP25
[O.D 32 mm
or more]
Supporter
700 mm or less
Horizontal or
upward gradient
Gap of 1.5-2 m
Prohibited
Air bleeding
Rise
Trap
Floor standing concealed setting
z
Prohibited
Trap
Drain cap
Rise
Install the drain pipe with downward gradient (1/50 to1/100) and so there are no rises or traps in the pipe.
Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm] and connect it with adhesive (polyvinyl
chloride) so that there is no leakage.
When the pipe is long. Install supporters.
Do not perform air bleeding.
Always heat insulate the indoor side of the drain pipe.