WIRED REMOTE CONTROLLER (UTY-RLR*)2-15.
REMOTE CONTROLLER ADDRESS SETTING2-15-1.
CONFIRM THE REMOTE CONTROLLER ADDRESS
1) Select the “15” in Menu 2 Settings.
Then press the [ENTER] button.
2) The address of this unit is displayed on the
screen.
” is displayed:
Address automatically
Remote controller address
allocated
Not displayed:
Address manually
allocated
01 to 32
Press the [ENTER] button to return to the Menu 2
item selection screen.
Note:
The address of this unit is set automatically. Do not change the indoor unit remote controller address from the
factory setting "0". (Verify that the address is "0".)
IF MANUALLY SETTING THE REMOTE CONTROLLER ADDRESS
1) Select the “15” in Menu 2 Settings.
Then press the [ENTER] button.
2) The address of this unit is displayed on the
screen.
Set the Unit Number with the [+] or [-] buttons.
System Number cannot be changed.
” is displayed:
Address automatically
Remote controller address
allocated
Not displayed:
Address manually
allocated
01 to 32
Press the [ENTER] button to return to the Menu 2
item selection screen.
Note:
Perform manual address setting only when setting the address with an arbitrary number. Indoor unit remote
controller address setting is necessary. Set the remote controller address of indoor units connected by the same
remote controller cable within a range of 1 to 9 and A (10) to F(15) so that there is no duplication. (Do not set to
"0".)
The address of this unit is set within a range of 1 to 32, but set it so that it does not duplicate the remote
controller address of an indoor unit connected by the same remote controller cable.
- (07-133) -
FUNCTION
SETTING
FUNCTION
SETTING