Apply voltage terminal TM201 (CN412)
z
When a power supply must be provided at the input device you want to connect, use the Apply
voltage terminal TM201 (CN412).
*A twisted pair cable(22AWG) should be used. Maximum length of cable is 25m.
P.C.B
TM201
K1
K2
K1
K2
CH1
+
+
-
-
+
-
CH2
CN201
CN412
(RED)
CN411
(WHITE)
DC power
supply 12V
P.C.B
CN412
(RED)
CN411
(WHITE)
CN410
(BLACK)
LAN
P.C.B
PANEL
*14
connected unit
*15
*16
*14 : Make the power supply DC12V.
*15 : Do not impress a voltage exceeding 12V across pins K1, and K2.
*16 : The allowable current is 10mA or less (Recommended : DC5mA).
INPUT SIGNAL TYPE
The input signal type can be selected.
Pulse
Edge
- (08 - 30) -
EXTERNAL INPUT
& OUTPUT
EXTERNAL INPUT
& OUTPUT