CONTROL INPUT FUNCTION
In the case of "Edge" input
Connector Input signal Command
Ch1 of
TM201
OFF → ON All on / Emergency stop
ON → OFF All off / Normal
Ch1 input
of TM201
Indoor unit
All on / Emergency stop
On
Off
All off / Normal
In the case of "Pulse" input
Connector Input signal Command
TM201
Ch1 OFF → ON All on / Emergency stop
Ch2 OFF → ON All off / Normal
Off
Off
On
On
TM201
Ch1 input
Ch2 input
Indoor unit
The width of pulse must be longer than 300msec.
All on / Emergency stop
All off / Normal
- (08 - 31) -