Network convertor setting (Set H)
Set the rotary switches 110 and 111 on the Network convertor PCB.
00
51
Group remote controller (Max. 4) *
2
Single split air conditioner
Network convertor for Group remote controller
(Max.16) *
1
Network convertor for Single split air conditioner
(Max.100) *
3
*
1
: The sum total of the
Touch panel controller, Central remote controller, Network convertor
for Group remote controller, Modbus convertor, and Network convertor for LonWorks is a max-
imum of 16.
*
2
: Up to 64 Group remote controllers are connectable in one VRF Network system.
*
3
: When connecting the Network convertor for single split air conditioner, set up the number
so that the refrigerant circuit address number of the outdoor unit and indoor unit does not
overlap. The sum total of the refrigerant circuit address of Network convertor for single split air
conditioner, outdoor unit and the indoor unit is a maximum of 100.
Dual remote control switch (Set J)
According to the number of connecting wired remote controller(s), turn “ON” or “OFF” the
switch 2 of DIP switch 1 on the slave remote controller.
2 wired remote controllers are
connected in a remote-control group
Only 1 wired remote controller is
connected in a remote-control group
Master Slave
Master
Switch 2 of DIP switch1
Master controller OFF OFF
Slave controller ON
When two wired remote controllers are connected in a remote-control group, turn the switch 2
of DIP switch 1 on the slave remote controller “ON”.
When only one wired remote controller is connected in a remote-control group, turn the switch
2 of DIP switch 1 on the slave remote controller “OFF”.
NOTES:
Timer setting is not available on the slave remote controller.
Last command takes priority.
1-3. Manual address setting method - (07-12) - 1. System settings