5.3 Preparations for Use
Take electrostatic prevention measures. Note that some carpets generate static electricity easily
and can cause the PRIMEPOWER400 Rackmount (4U) Server to malfunction.
When moving the PRIMEPOWER400 Rackmount (4U) Server, do not pull on the front cover.
Otherwise, the Server may be damaged.
5.3.2 Installation specifications
Table 5.2 and Table 5.3 show the installation specifications for the PRIMEPOWER400 Rackmount (4U) Server.
Table 5.2 Installation Specifications of the PRIMEPOWER400 Rackmount (4U) Server (1/2)
Item Specification
Weight 53 kg (116.99 lb.) (max.) (*1)
Power Supply
Voltage
Frequency 50/60 Hz (+2 ~ -4%)
Max. Current 8.9 A (100V)
Leak Current
Frame Resistance
Temperature Operating
Non-operating
Humidity Operating 20 ~ 80% RH (non-condensing)
Non-operating 8 ~ 80% RH (non-condensing)
Vibration Operating 0.2 G
Non-operating 0.4 G
Noise 50 db(A) (*3)
Form Factor Rackmount (4U)
3.7 A (240V)
Single phase
AC100 ~ 120V (
±
10%)
Single phase
AC200 ~ 240V(
±
10%)
²
3.5 mA
²
100
5 ~ 35
û
C (+41 ~ +95 F) (*2)
0 ~ 50
û
C (+32 ~ +122 F)
*1: Include Rack Rail weight.
*2: If the ambient temperature exceeds 35 deg. C (95 deg. F) during operation, a warning message is
displayed. Take steps to rectify the problem immediately.
*3: The indicated noise is the mean value of measurements obtained when the server unit is installed in
an 1800mm (71-inch) rack server in a low-noise anechoic chamber. The actual noise measured at
the installation site may be greater than the indicated value due to background noise and echoes.