91
 Network Definition 
Configuration
The devices within the address range written as Unused in Figure 51 cannot be used 
on a Fieldbus. For other address ranges, the range is periodically checked to identify 
when a new device is mounted. The address range cannot become wider, which can 
lead to exhaustive consumption of Fieldbus communication performance.
Figure 51 Available Range of Node Addresses
3. Ensure stable operation of Fieldbus by determining the operation parameters and 
setting them to the LM devices. The parameters in Table 13 must be set to the worst 
case value for all the devices connected to the same Fieldbus. Refer to the 
specification of each device for details. Table 13 lists FVP110 specification values.
Table 13 Operation Parameter Values of the FVP110 to be Set to LM Devices
Symbol Parameters Description
V (ST) Slot-Time Indicates the time necessary for immediate 
reply of the device. Unit of time is in octets (256 
s).
Set maximum specification for all devices. For 
FVP, set a value of 4 or greater.
V (MID) Minimum-Inter-PDUDelay Minimum value of communication data 
intervals. Unit of time is in octets (256 s). Set 
the maximum specification for all devices. For 
FVP, set a value of 4 or greater.
V (MRD) Maximum-Reply-Delay The worst case time elapsed until a reply is 
recorded. The unit is Slot-time; set the value so 
that V (MRD) 3V (ST) is the maximum value of 
the specification for all devices. For FVP, the 
setting must be a value of 12 or greater.