75
Standard Specifications
Standard Specifications
Pressure Gauge Case:
Stainless steel JIS SUS 304
Normal Operating Conditions:
Air Supply pressure:
❑ Single Acting Actuator: 20 to 60 psi (140 to 400 kPa)
❑ Double Acting Actuator: 30 to 100 psi (200 to 700 kPa)
Vibration Limit: 4 mm at 5 to 15 Hz; 2G at 15 to 2000 Hz
Shock limit: 10G
Manual Operation:
Available using Auto/Manual (A/M) transfer switch
Zero Adjustment Range:
–15 to 85% of span
Span Adjustment Range:
Within 300% of span
Valve-stem Travel Range:
❑ Linear Motion: 10 to 100 mm (0.4 to 4.0"), (Rotation Range: ±10 to ±25°)
❑ Rotary Motion: 20 to 90°
Table 6 Diaphragm, Double Acting Cylinder
Calibration
Unit
Supply Air
Pressure
Pressure Gauge Scale
Supply Air Output Signal
Pa
200 to 700 kPa 1 kPa 1 MPa
kgf/cm
2
2 to 7 10 10
bar
2 to 7 10 10
psi
30 to 105 150 150