FVP 110 Fieldbus Valve Positioner Manual
112
GE Energy
Alarm Generation
When the FVP110 detects an abnormality in the device using the self-diagnostic function,
a device alarm is issued from the resource or transducer block. An abnormality in a
function block or in a process value is issued from the corresponding block as a block
error or process alarm.
A FVP110 can report the following alarms and events.
Analog alerts A type of alarm generated when a process value or a deviation
value exceeds a specified limit in the following blocks: PID block :
HI, HI_HI, LO, LO_LO, DV_HI, DV_LO
Discrete alerts A type of alarm generated when an abnormal status is detected:
Resource block - a discrete alert is generated as a block
alarm or write-error alarm.
DI block - a discrete alert is generated as a block alarm or
DISC alarm.
Transducer, AO and PID block, a discrete alert is only
generated as a block alarm.
Update alerts Generated when a change is made to the settings of certain
parameters.
Table 28 shows the elements composing an alert object.
Table 28 Alert Objects
Subindex Parameter
Name
Description
Analog
Alert
Discrete
Alert
Update
Alert
1 1 1 Block Index
Leading Index to the block where the alert
occurs
2 2 2 Alert Key Copy of ALERT_KEY
3 3 3 Standard Type Type of the alert that occurred
444 Mfr Type
The name of the alert defined in the device
description (DD) file written by the device
manufacturer.
5 5 5 Message Type Cause of the alert
6 6 6 Priority Priority level of the alert
7 7 7 Time Stamp Time when the alert occurred first
8 8 Subcode Subcode that indicates the cause of the alert