FVP 110 Fieldbus Valve Positioner Manual
132
GE Energy
Control Parameters
The following FVP110 control parameters are set up by auto tuning (See “Description of
Control Parameters” on page 259):
* Applicable only for Double Acting Type
Temperature and Pressure Measurement
The FVP110 measures the surface temperature of the amplifier and sets it in the
transducer block parameter ELECT_TEMP. The unit of temperature is defined by
TEMPERATURE_UNIT and is selected from:
❑ 1101 = °C
❑ 1102 = °F
A FVP110 with an optional pressure sensor can measure the output air pressure to the
valve actuator and sets it in the parameter OUTPUT_PRESSURE. The unit of pressure is
defined by Unit Code in SPRING_RANGE and is selected from:
❑ 1133 = kPa
❑ 1137 = bar
❑ 1141 = psi
❑ 1145 = kgf/cm
2
SERVO_GAIN SERVO_RESET SERVO_RATE
SERVO_RATE_GAIN SERVO_DEADBAND SERVO_OFFSET
BOOST_ON_ THRESHOLD BOOST_OFF_ THRESHOLD BOOST_VALUE
SERVO_I_SLEEP_LMT SERVO_P_ALPHA INTERNAL_GAIN
X_BOOST_ON_ THRESHOLD * X_BOOST_OFF_ THRESHOLD * X_BOOST_VALUE *