Parameters of Transducer Block
Function Block Parameters
6 2006 BLOCK_ERR Indicates the error statuses related to the block
itself.
7 2007 UPDATE_
EVT
Shows the contents of an update event upon
occurrence.
8 2008 BLOCK_ALM Universal parameter indicating the hardware
and software error statuses related to the block
itself.
9 2009 TRANSDUCE
R
_DIRECTOR
Y
1, 10 Index to the text describing the transducer
contained in the FVP110 positioner.
10 2010 TRANSDUCE
R_TYPE
106 Transducer type.
11 2011 XD_ERROR 0 Stores the error prioritized at the highest level
from among the errors that are currently
occurring in the transducer block.
12 2012 CORRECTIO
N
_DIRCTORY
1, 13 Stores the number of data collection and the
index number to be started with.
13 2013 FINAL_
VALUE
O/S Stores the valve control level and status written
by the AO block.
14 2014 FINAL_
VALUE
_RANGE
-10%, 110% O/S Defines the upper and lower range limits of
FINAL_VALUE, and the unit code and decimal
point position for value indication of
INAL_VALUE.
15 2015 FINAL_
VALUE
_CUTOFF_HI
110% O/S If the value of FINAL_VALUE is greater than
the value set in this parameter, the FVP110
moves the valve to the full-open position.
16 2016 FINAL_
VALUE
_CUTOFF_
LO
-10% O/S If the value of FINAL_VALUE is less than the
value set in this parameter, the FVP110 moves
the valve to the shut-off position.
17 2017 FINAL_
POSITION
_VALUE
Stores the position data read by the valve
position sensor.
Table 61 Transducer Block Parameters (Continued)
Relative
Index
Index Parameter
Name
Default
(factory
setting)
Write Description