FVP 110 Fieldbus Valve Positioner Manual
76
GE Energy
Air Consumption and Output Capacity:
\
Ambient Temperature Limits:
❑ Single Acting Actuator: –40 to 85 °C (–40 to 185 °F)
❑ Double Acting Actuator: –40 to 60 °C (–40 to 140 °F) for standard, –10 to 85 °C
(14 to 185 °F) for high temperature use with option code /HT
Ambient Humidity Limits:
5 to 95% RH at 40 °C (104 °F)
EMC Conformity Standards:
EN61326, AS/NZS CISPR11
Degrees of Protection:
IP65, NEMA4X
Connections:
❑ Air Connection: 1/4 NPT female
❑ Electrical Connection: 1/2 NPT, M20
❑ Pressure Gauge Connection:
Table 7 Diaphragm, Single Acting Cylinder
Parameter Value
Maximum Air Consumption 0.20 SCFM (0.32 Nm3/h) at 140 kPa
Maximum Output Capacity 4.1 SCFM (6.6 Nm3/h) at 140 kPa
Table 8 Diaphragm, Double Acting Cylinder
Parameter Value
Maximum Air Consumption 0.62 SCFM (1.0 Nm3/h) at 400 kPa
Maximum Output Capacity 8.5 SCFM (13.7 Nm3/h) at 400 kPa