FVP 110 Fieldbus Valve Positioner Manual
264
GE Energy
INTERNAL_GAIN
Tuning range: 0.5 to 50 rad/mA (Default: 5 rad/mA)
INTERNAL_GAIN is the total gain of the I/P module, the control relay, the valve, the
actuator, and the feedback lever.
INTERNAL_GAIN is part of the loop gain of PI-D control.
This value is usually determined by Auto Tuning, so you do not need to change the value.