FVP 110 Fieldbus Valve Positioner Manual
30
GE Energy
*1: The third figure from the last of the serial number shows the year of production. For
example, the production year of the product engraved in NO. column on the name plate
as follows is 2001.
Figure 11 Production Year
*2: 180-8750 is a zip code which represents the following address: 2-9-32 Nakacho,
Musashino-shi, Tokyo Japan
CSA Certification
A) CSA Explosionproof Type
Cautions for CSA Explosionproof type.
Note 1. Model FVP110 Advanced Valve Positioner with optional code /CF1 are
applicable for use in hazardous locations:
❑ •Applicable standard: C22.2 No. 0, No. 0.4, No. 0.5, No. 25, No. 30, No. 94, No.
1010.1
❑ Certificate: 1186507
❑ Explosionproof for Class I, Groups B, C and D; Class II, Groups E, F and G; Class
III.
❑ Enclosure Rating: Type 4X
❑ Temperature Code: T6 and T5
❑ Ambient Temperature: –40 to 75 °C for T6, –40 to 82 °C for T5
Note 2. Wiring
❑ All wiring shall comply with National Electrical Code ANSI/NFPA 70 and Local
Electrical Codes.
❑ FACTORY SEALED, CONDUIT SEAL NOT REQUIRED.
❑ When the ambient temperature is 60 °C or more, use an external cable having a
maximum allowable heat resistance of at least 90 °C.
Note 3. Maintenance and Repair
❑ The instrument modification or parts replacement by other than authorized
representative of GE Masoneilan is prohibited and will void CSA Certification.