FVP 110 Fieldbus Valve Positioner Manual
24
GE Energy
or
EEx ia IIB T4
Maximum Voltage (Ui) = 17.5 V
Maximum Current (Ii) = 380 mA
Maximum Power (Pi) = 5.32 W
Internal Capacitance (Ci) = 1.76 nF
Internal Inductance (Li) = 0 μH
Number of Devices
The number of devices (max. 32) possible on a fieldbus link depends on factors such as
the power consumption of each device, the type of cable used, use of repeaters, etc.
Entity Model
Figure 7 Entity Model
I.S. fieldbus system complying with Entity model
I.S. values Power supply-field device:
Po Pi, Uo Ui, Io Ii
Calculation of max. allowed cable length:
Ccable Co - Σci - Σci (Terminator)
Lcable Lo - ΣLi