267
 Installation of Flameproof 
Installation and Operating
Installation of Flameproof Apparatus
Installation Area Flameproof apparatus may be installed, in accordance with 
applicable gases, in a hazardous area in Zone 1 or 2, where the 
specified gases are present. Those apparatus shall not be 
installed in a hazardous area in Zone 0.
Hazardous areas are classified in zones based upon the fre-
quency of the appearance and the duration of an explosive gas 
atmosphere as follows:
Zone 0: An area in which an explosive gas atmosphere is pres-
ent continuously or is present for long periods.
Zone 1: An area in which an explosive gas atmosphere is likely 
to occur in normal operation.
Zone 2: An area in which an explosive gas atmosphere is not 
likely to occur in normal operation and if it does occur it will exist 
for a short period only.
Environmental 
Conditions
The standard environmental condition for the installation of 
flameproof apparatus is limited to an ambient temperature 
range from –20 °C to +40 °C (for products certified under Tech-
nical Criteria). However, some field-mounted instruments may 
be certified at an ambient temperature up to +60 °C as indi-
cated on the instrument nameplates. If the flameproof appara-
tus are exposed to direct sunshine or radiant heat from plant 
facilities, appropriate thermal protection measures shall be 
taken.
External Wiring for Flameproof Apparatus
Flameproof apparatus require cable wiring or flameproof metal conduits for their 
electrical connections. For cable wiring, cable glands (cable entry devices for 
flameproof type) to wiring connections shall be attached. For metal conduits, attach 
sealing fittings as close to wiring connections as possible and completely seal the 
apparatus. All non-live metal parts such as the enclosure shall be securely grounded. 
For details, see the USER’S GUIDELINES for Electrical Installations for Explosive Gas 
Atmospheres in General Industry, published in 1994.
Cable Wiring
❑ For cable wiring, cable glands (cable entry devices for flameproof type) specified 
or supplied with the apparatus shall be directly attached to the wiring connections 
to complete sealing of the apparatus.
❑ Screws that connect cable glands to the apparatus are those for G-type parallel 
pipe threads (JIS B 0202) with no sealing property. To protect the apparatus from