FVP 110 Fieldbus Valve Positioner Manual
232
GE Energy
Transducer Block
Setup Wizard
This method guides you through each step of the most common setup procedure that
always needs to be performed after installing the FVP110 on a valve. For the details of
the setup and pertaining parameters, see “Setup” on page 59.
Setup procedure:
4. AO/TB block mode check
5. ACT_FAIL_ACTION setting
6. VALVE_TYPE setting
7. Stop position search and automatic tuning
8. Travel calibration
0% calibration
Span calibration
50% calibration
9. Operational parameter setting
10.
Auto Tuning Wizard
This method guides you through each step to search for the valve’s mechanical stop
positions and carry out auto tuning of control parameters. For details, see “Carrying out
Tuning” on page 61.
Auto tuning procedure
1. AO/TB block mode check
2. Auto tuning execution: AUTO_TUNE_EXEC