Troubleshooting
What to Do First
When a problem occurs, check the following first.
Mounting of FVP110 positioner:
Is the linkage to the valve actuator correctly set up?
Is the feedback lever correctly attached?
Is the span of rotation angle of the position sensor against the valve stroke more than
the minimum requirement?
Has auto tuning been performed after installation?
Air Piping:
Are the air pipes correctly connected? Is there no leak of air?
Is the air supply pressure high enough to drive the valve?
Is the A/M selector on the positioner set to A (automatic)?
Wiring:
Is the FVP110 positioner correctly connected to the fieldbus?
Are the conductors incorrectly connected, in other words, is the plus side connected
to minus, and vice-versa?
Has the power to the fieldbus been turned on? Is the terminal-to-terminal voltage
equal to or greater than 9 V?
Is the terminator correctly installed?
Is a host system connected to the fieldbus?