FVP 110 Fieldbus Valve Positioner Manual
234
GE Energy
Operational Parameter Configuration
This method guides you through the setting of individual operational parameters
excluding the selection of position to-flow rate characteristic type.
Operational parameter configuration procedure:
1. AO/Transducer block mode check
2. Operational parameter configuration
a. Position Limit setting: FINAL_VALUE_CUTOFF_LO
❑ FINAL_VALUE_CUTOFF_HI
❑ FINAL_VALUE_RANGE
b. Limit Switch setting:
❑ LIM_SW_LO_LIM
❑ LIM_SW_HI_LIM
c. Fault Control:
❑ DEVIATION_LIM
❑ DEVIATION_TIME_TH(1)
❑ DEVIATION_TIME_TH(2)
d. Others:
❑ NEAR_CLOSE_THRESHOLD
e. Exit
Release Fail Safe
This is a method for releasing the device latched by the fail-safe actions, restoring it to the
normal state.
Procedure of releasing fail safe:
1. Check whether the device is in the latched state.
2. Write Clear-latched to parameter RELEASE_FAIL_SAFE if the device is in the latched
state, to release it from the latched state.