EasyManua.ls Logo

GE FVP110 - Troubleshooting AutoTuning

GE FVP110
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
165
STATUS_OPTS
PID Function Block
STATUS_OPTS
Table 50 shows the options in STATUS_OPTS.
Auto Fallback
Auto fallback is when a PID block changes mode from Cas to Auto and continues
automatic PID control with the user-set setpoint. To enable the auto fallback action to
take place:
The Target to next permitted mode if BAD CAS IN option must be preset to true
in STATUS_OPTS.
AND
Auto must be preset in MODE_BLK.permitted.
If the above settings are made, auto fallback takes place automatically when the
following condition is met:
CAS_IN.status (data status of cascade setpoint) is Bad except when the control
action bypass is on.
Table 50 STATUS_OPTS of PID Block
Bit Options in CONTROL_OPTS Description
0
IFS if BAD IN Sets the sub-status component of OUT.status to IFS if IN.status
is Bad except when PID control bypass is on.
1
IFS if BAD CAS IN Sets the sub-status component of OUT.status to IFS if
CAS_IN.status is Bad.
2
Use Uncertain as Good Does not regard IN as being in Bad status when IN.status is
Uncertain (to prevent mode transitions from being affected
when it is Uncertain).
5
Target to Manual if BAD IN Automatically changes the value of MODE_BLK.target to Man
when IN falls to Bad status.
9
Target to next permitted mode
if BAD CAS IN
Automatically changes the value of MODE_BLK.target to Auto
(or to Man if Auto is not set in Permitted) when CAS_IN falls to
Bad status.

Table of Contents

Related product manuals