FVP 110 Fieldbus Valve Positioner Manual
188
GE Energy
*1: FF-891 “Foundation
TM
Specification Function Block Application Process Part 2”
Parameters of Transducer Block
Parameters marked with (*1) are automatically set and changed by autotuning.
Parameters marked with (*2) are automatically set and changed by Travel calibration.
51 1051 DEVICE_STA
TUS_7
0 Not used in the FVP110.
52 1052 DEVICE_STA
TUS_8
0 Not used in the FVP110.
Table 61 Transducer Block Parameters
Relative
Index
Index Parameter
Name
Default
(factory
setting)
Write Description
0 2000 Block Header Block Tag
=O/S
Information about this block, including the
block tag, DD revision, execution time
1 2001 ST_REV 0 Incremented when a change is made to the
parameter settings for the resource block to
indicate the revision level of the settings, and
used to see whether or not there is a change in
parameter settings.
2 2002 TAG_DESC Spaces Universal parameter storing the description of
the tag
3 2003 STRATEGY 1 Universal parameter used by an upper-level
system to classify the function blocks
4 2004 ALERT_KEY 1 Universal parameter used as a key to identify
the point from which an alert is issued;
normally used by an upper level system to
select alerts to provide to a particular operator
who covers a specific area of the plant.
5 2005 MODE_BLK O/S Universal parameter that indicates the block
operation conditions and is composed of actual
mode, target mode, permitted modes, and
normal mode.
Table 60 Resource Block Parameters (Continued)
Relative
Index
Index Parameter
Name
Default
(factory
setting)
Write Description