FVP 110 Fieldbus Valve Positioner Manual
96
GE Energy
Block Setting
Set the parameter for the VFD function block.
Link Object
Link object combines the data voluntarily sent by the function block with VCR. FVP110
has 25 non-factory set link objects. A single link object specifies one combination. Each
link object has the parameters listed in Table 15. Change parameters together for each
VCR, as modifications made to each parameter can cause inconsistent operation.
Table 15 Execution Schedule of the FVP110 Function Blocks
Sub-index Parameters Description
1 LocalIndex
Sets the index of function block parameters to
be combined; set 0 for Trend and Alert.
2 VcrNumber
Sets the index of VCR to be combined. If set to
0, this link object is not used.
3 RemoteIndex
Sets the index of remote object associated with
this link object.
4 ServiceOperation
Set one of the following. Set only one each for
link object for Alert or Trend.
0: Undefined
1: Local
2: Publisher
6: Alert
7: Trend
5 StaleCountLimit
Set the maximum number of consecutive stale
input values before the input status is set to
BAD.
Setting 2 or larger avoids unnecessary mode
transfer caused when subscriber failed to
receive data correctly.