FVP 110 Fieldbus Valve Positioner Manual
178
 GE Energy
Troubleshooting Valve Control
Table 57 Troubleshooting Valve Control
Problem Presumed Cause Remedy See Section
A change in setpoint 
causes no action of the 
valve.
Air piping is incorrect. Correct piping.  “Piping” on 
page 52
The instrument is in FAILSAFE 
state.
Write Clear non-latch to 
RELEASE_FAILSAFE 
parameter.
 “Fail-safe Action” 
on page 131
Air supply is not being fed. Supply proper air 
pressure.
 “Piping” on 
page 52
The valve has failed. Apply a pneumatic 
pressure directly to the 
valve actuator and check 
whether there is valve 
action.
 “A/M Switching” 
on page 42
The I/P module or control relay 
has failed, or there is breakage 
in the cable between the I/P 
module and control relay.
If the output pressure does 
not increase even though 
the 
SERVO_OUTPUT_SIGN
AL value is at maximum, 
contact the nearest 
service station or 
representative office.
—
The valve’s full stroke is 
insufficient for the setpoint 
input.
The air supply pressure is not 
high enough to drive the valve 
actuator.
Check the air supply 
pressure rating for the 
valve actuator and supply 
air at the correct pressure, 
and write 4 or 2 to 
AUTO_TUNE_EXEC to 
redo Autotuning.
❑  “Piping” on 
page 52
❑  “Carrying out 
Tuning” on 
page 61
The range of the setpoint is 
limited by software.
Check the values of 
SP_HI_LIM and 
SP_LO_LIM in the AO 
block and 
FINAL_VALUE_RANGE in 
the transducer block.
❑  “Forward 
Path” on 
page 134
❑  “Function 
Block Parame-
ters” on 
page 183