FVP 110 Fieldbus Valve Positioner Manual
128
GE Energy
(*1) Number 103 is not shown for AUTO_TUNE_RESULT. Number 1 through 44 and 120
through 123 are not shown for TRAVEL_CALIB_RESULT.
(*2) E stands for Error, and W stands for Warning.
62
50% angle warning
W
VALVE_TYPE is linear and the rotation angle at the 50%
position exceeds ±20°.
100 Small angle span error W Rotation-angle span < 5°.
101
Large angle span error
E
VALVE_TYPE is linear and the rotation-angle span exceeds
60°; or VALVE_TYPE is rotary and the rotation-angle span
exceeds 100°.
102
50% angle error
E
VALVE_TYPE is linear and the rotation angle at the 50%
position exceeds ±25°.
103
Linear adjust error
E
FINAL_VALUE.value falls outside 50 ±10% at 50%
position.
120
Offset measurement failed
error
E
Offset measurement has failed.
121
Gain measurement failed
error
E
Gain measurement has failed.
122
Response speed
measurement failed error
E
Response speed measurement has failed.
123
Hysteresis measurement
failed error
E
Hysteresis measurement has failed.
255 In operation Auto tuning is being executed.
Table 35 AUTO_TUNE_RESULT & TRAVEL_CALIB_RESULT (Continued)