EasyManua.ls Logo

GE FVP110 - Function Block Parameters

GE FVP110
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
167
Alarms
PID Function Block
(*1) The modes to which the PID block can transfer are limited to those set in
MODE_BLK.permitted, and the priority levels of modes (Figure 75). In fact, if Normal
shed, normal return is set for SHED_OPT, detection of a computer failure causes
MODE_BLK.actual to change to Cas, Auto, or Man, whichever is set in
MODE_BLK.permitted and has the lowest priority level.
Figure 75 Priority Levels
(*2) Only when Auto is set as permitted mode.
NOTE If a control block is connected as a cascade primary block of
the PID block in question, a mode transition of the PID block
to Cas occurs in the following sequence due to initialization
of the cascade connection: RCas or ROut —> Auto —>
Cas.
Alarms
There are two kinds of alarms generated by a PID block: block and process alarms.
Block Alarm (BLOCK_ALM)
The block alarm BLOCK_ALM is generated on occurrence of the errors in Table 52
(values set in BLOCK_ERR) and notifies the content of BLOCK_ERR.
Table 52 Block Alarm (BLOCK_ALM)
Value of BLOCK_ERR Condition
Input Failure
IN.status of the PID block is either of the following:
Bad-Device Failure
Bad-Sensor Failure
Local Override MODE_BLK.actual of the PID block is LO.
Out of Service MODE_BLK.target of the PID block is O/S.

Table of Contents

Related product manuals