CENELEC ATEX (KEMA)
Safety
Note 1.
Use dust-tight conduit seal when installed in Class II and Class III environments.
Note 2.
Install in accordance with National Electrical Code (ANSI/NFPA 70) Sections 504, 505
and Local Electrical Code.
Note 3.
The configuration of Associated Apparatus must be Factory Mutual Research
Approved.
Note 4.
Follow the Associated Apparatus manufacturer's installation drawing when installing.
Note 5.
No revision to drawing without prior Factory Mutual Research Approval.
Note 6.
Terminator and supply unit must be FM approved.
Note 7.
Installation requirements:
Vmax Voc or Vt
Ca Ci + Ccable
La Li + Lcable
CENELEC ATEX (KEMA) Certification
Technical Data
A) CENELEC ATEX (KEMA) Intrinsically Safe Type Caution for CENELEC ATEX (KEMA) Intrinsically Safe
Type.
WARNING Do not open the cover when energized.
When the ambient temp.70 °C, Use the heat-resisting
cable 90 °C
NOTE Keep the safety use conditions for 1GD when used in the
hazardous gas and dust area.

Table of Contents