219
Transfer of LAS
Link Master Functions
To set up a FVP as a device that is capable of backing up the LAS:
CAUTION When changing the FVP settings, add the FVP to the
segment in which an LAS is running. After making changes
to the settings, do not turn off the power to the FVP for at
least 60 seconds.
1. Set the node FVP address. In general, use an address from 0x10 to [V(FUN) - 1].
Figure 78 Node Address Ranges
2. Set the FVP LAS settings for V(ST), V(MRD), and V(MID) to the same as the
respective lowest capability values in all the devices within the segment. An
example is shown in Figure 79.
Figure 79 DlmeBasicInfo (YVP Index 361 (SM)) Example
In this case, set SlotTime, MaxResponseTime, and MinInterPduDelay as follows
(Figure 80).