FVP 110 Fieldbus Valve Positioner Manual
190
GE Energy
18 2018 SERVO_
GAIN (*1)
120 O/S Static control loop gain set by auto tuning [0.5
to 1300 ]
19 2019 SERVO_
RESET (*1)
15 sec O/S Integral time set by auto tuning.
20 2020 SERVO_
RATE (*1)
0. 22 sec O/S Derivative time set by auto tuning.
21 2021 ACT_FAIL_
ACTION
1 O/S Specifies the actuator action direction (in case
of losing of air supply pressure):
1 = Air to Open
2 = Air to Close
22 2022 ACT_MAN_ID 0
ID of actuator manufacturer
23 2023 ACT_MODEL
_NUM
Null
Model number of actuator
24 2024 ACT_SN 0
Serial number of actuator
25 2025 VALVE_MAN
_ID
0—
ID of valve manufacturer
26 2026 VALVE_
MODEL
_NUM
Null Model number of valve
27 2027 VALVE_SN 0 Serial number of valve
28 2028 VALVE_TYPE 1 O/S Valve type:
1 = linear-motion valve
2 = rotary-motion valve
29 2029 XD_CAL_
LOC
Null Shows and is used to record the location where
the positioner was calibrated.
30 2030 XD_CAL_
DATE
01/01/00 Shows and is used to record the date when the
positioner was calibrated.
31 2031 XD_CAL_
WHO
Null Shows and is used to record the person who
calibrated the positioner.
32 2032 ALARM_
SUM
Shows the alarm summary (current alarm
statuses, acknowledged/unacknowledged
states, masking states) for the transducer
block.
Table 61 Transducer Block Parameters (Continued)
Relative
Index
Index Parameter
Name
Default
(factory
setting)
Write Description