191
Parameters of Transducer Block
Function Block Parameters
33 2033 POSITION_
CHAR
_TYPE
1 O/S Defines the valve position-to-flow
characteristics:
1 = linear
2 = equal % (50:1)
3 = equal % (30:1)
4 = quick open (inverse of 50:1 equal %)
5 = Camflex Percentage
255 = user-defined 10-segment function
34 2034 POSITION_
CHAR
10,20,30,40,5
0,60,
70,80,90
O/S Defines the coordinates of the segment
function when 255 is set for
POSITION_CHAR_TYPE.
[0 to 100, only simple decreasing can be
allowed]
35 2035 LIMSW_HI_
LIM
+110% Setting of high limit switch
36 2036 LIMSW_LO_
LIM
-10% Setting of low limit switch
37 2037 ELECT_
TEMP
– — Indicates the temperature on amplifier board
38 2038 TEMPERATU
RE
_UNIT
1101(°C) O/S Defines the unit of temperature indication
above:
1101 = °C
1102 = °F
39 2039 SUPPLY
_PRESSURE
140 kPa O/S Air supply pressure (irrespective of control)
40 2040 SPRING_
RANGE
20 kPa, 100
kPa
O/S Defines the pressure range and unit for valve
operation (with no direct effect on control). The
unit defined here also applies to
OUT_PRESSURE.
1133 = kPa
1137 = bar
1141 = psi
1145 = kgf/cm
2
41 2041 OUT_
PRESSURE
– — Output pressure to valve actuator
Table 61 Transducer Block Parameters (Continued)
Relative
Index
Index Parameter
Name
Default
(factory
setting)
Write Description